COOPERATOREVENTS NEW YORK EXPO. TUESDAY NOV 19TH . JAVITS CONVENTION CENTER. REGISTER NOW!

Energy Auditing Your Building How Good is Your Local Law 87 Report?

Energy Auditing Your Building

 There are a number of consultants out there that are “pretending” that they can prepare the energy audit and energy efficiency reports required  by Local Law 87.  

 Local Law 87 of New York City's Greener, Greater Buildings Plan requires all  buildings over 50,000 square feet to file an Energy Efficiency Report (EER)  with the New York City Department of Buildings. The EER consists of an ASHRAE  Level II energy audit and retro-commissioning study of base building systems.  

 Energy Efficiency Reports are due once every ten years. The first reports must  be filed by 2013, and are due in a staggered schedule based on the last digit  of the building's tax block number. Both the energy audit and  retro-commissioning study must be completed within four years before the EER is  filed.  

 I had the recent unfortunate opportunity to review an energy efficiency report  that was poorly prepared and of almost no use to the client.  

 Be Prepared

 Needless to say, you cannot wait until December 1, 2013 to start preparing a  report due on December 31, 2013. It may take your consultant several months to  prepare the energy audit report, and in some cases, it might take 6 to 18  months to fully implement the recommendations.  

 The energy audit report is supposed to tell you what operations and maintenance  work, and capital improvements, are needed in the building to reduce energy  use. Once you get the energy audit report, you are required by Local Law 87 to  complete the retro-commissioning work.  

 Some of the work may be minor, for example, a boiler cleaning. Other work may be  major, for example, replacement of an oversized boiler—in which case, it might take an engineer several months to select a smaller  boiler. It can take from 6 to 18 months from start to finish to complete a  major job such as this.  

 What can go wrong? As Murphy’s Law tells you, almost everything. Let’s start with some basics:  

 The energy audit report should have a page summarizing energy usage and costs  for the past one or two years for fuel oil, natural gas and electricity. It  should also provide a baseline cost of each of the units of energy to be used  in the report’s calculations.  

 For the cost of oil, the question is whether to use the present cost of the last  delivery or the average cost over the past year. I recommend to use the most  recent cost, as it is difficult to predict the future cost of oil. If the last  delivery was several months ago, I prefer to call up the supplier and use the  present cost.  

 For natural gas, your consultant should not use an average cost per therm from  the last bill, but rather should look at the incremental cost of the last therm  of gas, plus any applicable taxes and surcharges.  

 For electricity, if you are billed for energy and demand charges, your  consultant should break down these charges. There may be distortions in the  energy cost savings calculations for certain energy conservation measures. For  example, an energy conservation measure involving lighting that is on 24 hours  a day, 7 days a week may distort the cost savings if an average cost per kWh is  used in the calculations.  

 Each energy conservation measure should be on a separate page. It should begin  by describing the present condition. It should describe the recommended energy  conservation measure. Energy saving calculations must be based on sound  science. It should provide a verifiable calculation showing how much energy  will be saved by the measure. A cost estimate needs to be provided for the  energy conservation measure, and a basis for the cost. A simple payback period  needs to be provided.  

 Energy conservation measures should not engage in double accounting of energy  savings. For example, tuning up a boiler may raise its steady state efficiency  from 75 to 80 percent. A calculation for the energy savings to insulate a steam  line should be based on the 80 percent efficiency rate, not the 75 percent  efficiency.  

 Is Your Heating System Oversized?

 The report that I saw had a calculation for replacing a 5-ton lobby air  conditioning system with a more efficient system. There was no load calculation  to determine if the 5-ton A/C system was oversized. And in this case, a smaller  system may have been more efficient and cheaper to install.  

 Also, the basis for the energy savings calculation was based on a guess of the  number of hours the system was running; it was not based on any actual  measurements. It was assumed that the system was running continuously; A/C  systems do cycle. The fan may run continuously, but the compressor may cycle.  Also, the cost of the installation was too low, making the potential payback  period appear shorter than reality. Additionally, no mention was made of a need  to clean the ductwork.  

 Another factor is that the heating description was incomplete. The report  mentioned the make and model of the steam boiler, but did not tell whether it  was a one-pipe or two-pipe steam system. No mention was made of whether the  boiler had adequate insulation. There was also no inventory of the uninsulated  steam lines; I have yet to see a building in New York City which has adequate  steam pipe insulation. If your boiler room is over 65 degrees, your boiler or  your steam lines, or both, do not have adequate insulation. No mention was made  if the outside air to supply the boiler room had a solenoid-activated damper in  series with the boiler controls to keep cold air out of the boiler room when  the boiler is off.  

 It was also not clear if the boiler was oversized for the building. No inventory  was made of the attached steam radiators to determine the total BTUs necessary  to get steam to all of the radiators at the same time. One must compare the attached radiation load against the firing rate of the  boiler. It was not clear if the radiators were oversized; once you put  double-glazed windows in a building, your radiators become immediately  oversized which leads to overheating situations. In this case, you need to put  smaller radiators in the building. Thermostatic radiator valves can be great,  but sometimes putting in smaller radiators is actually much cheaper.  

 Any calculation that is based on a “percentage” must be treated as suspect. Any consultant that relies on manufacturer’s literature rather than sound engineering principles can be prone to  inaccuracies in their reports. My advice is to question everything. Use best  practices and practical engineering rather than guesswork to avoid any problems  down the line.    

 Daniel Karpen is a Long Island-based professional engineer and consultant.  

Related Articles

Reduce CO2 emissions to limit climate change and global warming. Low greenhouse gas levels, decarbonize, net zero carbon dioxide footprint. Abstract minimalist design, cutout paper, green background.

Navigating Building Decarbonization in New York State

Strategies for Multifamily Boards and Property Owners

A Red folder with Emergency response plan on the desk.

Emergency Preparedness in the Era of Climate Change

Preparing for the Unpredictable

Climate-neutral long-term strategy greenhouse gas emissions targets Wooden block with green net center icon. Carbon neutral and net zero concept natural environment.

Saving Money and Slowing Climate Change

NY State’s Value Distributed Energy Resources Program

 

2 Comments